Key takeaways
- At Denver's elevation the air is roughly 15–16% less dense than at sea level. That affects every part of an HVAC system: burner combustion, fan airflow, and how much heat each cubic foot of air can carry.
- Gas furnaces must be derated. Amana and Goodman manuals call for reducing input 4% for every 1,000 feet of elevation once above 2,000 feet. At 5,280 feet that's about 21%, so an 80,000 Btu/h furnace fires at roughly 63,000.
- Derating is done with smaller orifices, a high-altitude pressure switch or kit, or gas the utility already delivers at lower heat content. It is never done by turning down manifold pressure below the nameplate value.
- ACs and heat pumps lose capacity too. NREL measured 5.5–7.4% less heat pump capacity in Golden. Fujitsu's bulletin lists a 0.83 factor at 5,000 feet. Manufacturer data, not sea-level catalog numbers, should drive sizing.
- A furnace set up wrong for altitude can produce carbon monoxide. Insist on a combustion analysis at startup, plus working CO alarms.
- Elevation varies a lot across the Front Range: from about 4,700 ft in Greeley to 6,371 ft in Castle Pines and over 8,000 ft in Nederland.
Most HVAC equipment sold in the U.S. is designed and rated at sea level. Put that same furnace, air conditioner or heat pump in Castle Rock or Evergreen and it behaves differently. Burners get less oxygen, fans move thinner air, and the published capacity on the label no longer matches what the system delivers.
None of this means equipment doesn't work at altitude. Millions of Coloradans heat and cool their homes just fine. It means installation has to account for elevation, and a contractor who skips that step can leave you with an undersized system, a furnace that runs rich, or both. This guide explains what changes between 5,000 and 8,000 feet, and what to ask for.
Why thin air matters
Air pressure and density fall as you climb. Air at Denver's elevation is about 15–16% less dense than at sea level. By the U.S. Standard Atmosphere, the gap grows to roughly a fifth around 8,000 feet. Three things follow:
- Less oxygen per cubic foot for burning gas.
- Less heat per cubic foot of air. A fan moving 1,000 cfm in Denver moves fewer pounds of air than the same fan in Houston, so it carries less heat to or from your rooms.
- Lower pressure across gas orifices and coils, which changes how much fuel flows and how refrigerant coils transfer heat.
ACCA's Manual J load calculation includes an altitude correction factor for this. An ACHR News design example uses 0.84 at 5,000 feet for heating airflow calculations and about 0.92 for a dry cooling coil. The same article shows that carrying 36,000 Btu/h of sensible heat takes about 1,200 cfm at sea level but about 1,430 cfm at 5,000 feet. Air volume doesn't change with elevation; the heat it can carry does.
Front Range elevations
"Denver altitude" is a shorthand. The mile marker on the Capitol steps is 5,280 feet, but the metro spans well over 1,500 feet of elevation, and foothills communities sit far higher. Here's how USGS reference elevations compare, with what they mean for a furnace derate and one manufacturer's heat pump capacity factors.
| Town | Elevation (ft, USGS GNIS) | Furnace input derate at 4% per 1,000 ft* | Fujitsu heat pump capacity factor** |
|---|---|---|---|
| Greeley | 4,675 | 19% | 0.84 |
| Longmont | 4,980 | 20% | 0.83 |
| Fort Collins | 5,003 | 20% | 0.83 |
| Erie | 5,026 | 20% | 0.83 |
| Lafayette | 5,210 | 21% | 0.82 |
| Denver | 5,280 | 21% | 0.82 |
| Boulder | 5,318 | 21% | 0.82 |
| Thornton | 5,348 | 21% | 0.82 |
| Littleton | 5,351 | 21% | 0.82 |
| Westminster | 5,381 | 22% | 0.82 |
| Aurora | 5,404 | 22% | 0.82 |
| Lakewood | 5,518 | 22% | 0.81 |
| Golden | 5,673 | 23% | 0.81 |
| Morrison | 5,764 | 23% | 0.81 |
| Centennial | 5,837 | 23% | 0.80 |
| Parker | 5,869 | 23% | 0.80 |
| Lone Tree | 5,997 | 24% | 0.80 |
| Colorado Springs | 6,010 | 24% | 0.80 |
| Castle Rock | 6,217 | 25% | 0.79 |
| Castle Pines | 6,371 | 25% | 0.79 |
| Monument | 6,975 | 28% | 0.77 |
| Evergreen | 7,162 | 29% | 0.77 |
| Idaho Springs | 7,526 | 30% | 0.75 |
| Nederland | 8,232 | 33% | 0.73 |
*Calculated using the method in Amana and Goodman furnace manuals and the ACHR News example (4% of input per 1,000 feet of elevation once above 2,000 feet). Your furnace's manual governs; some use different schedules. **Interpolated from Fujitsu's Airstage high-altitude bulletin (heating and cooling); other brands differ. Elevations are the GNIS reference point for each town, from Wikipedia's list of Colorado municipalities by elevation (Evergreen from its Wikipedia entry). Your street can be hundreds of feet higher or lower.
Gas furnaces: combustion derate, orifices and pressure switches
Why a furnace has to be derated
A gas burner needs the right mix of fuel and air. At altitude there is less oxygen in each cubic foot of combustion air. Feed a burner its full sea-level gas rate and it runs rich: it burns incompletely, the heat exchanger runs hotter, and carbon monoxide rises. ACHR News notes that a furnace's input depends on the pressure drop across the gas orifice and on the density and oxygen content of the combustion air, and altitude affects all three.
The fix is to reduce the gas input. The rule in the manuals we reviewed:
- Amana: above 2,000 feet, derate input 4% for each 1,000 feet above sea level. Smaller orifices are needed above 3,500 feet on natural gas the supplier hasn't already derated, and a different pressure switch is required above 4,000 feet.
- Goodman: the same 4% per 1,000 feet, noting that installations above 4,500 feet usually need an orifice change and some models need a pressure switch change.
- ACHR News example: an 80,000 Btu/h-input furnace at 5,000 feet derates to 64,000 Btu/h input. At 80% steady-state efficiency, that's about 51,200 Btu/h of heat delivered.
Schedules vary by manufacturer and model, and ACHR has reported that some premium models need only 2% per 1,000 feet. Always follow the installation manual for the specific furnace.
Orifices, gas heat content and "clocking the meter"
Here's a wrinkle many homeowners never hear about. In some areas the gas utility delivers gas with a lower heating value per cubic foot at altitude, which accomplishes part of the derate before the gas reaches your furnace. Amana's manual notes that "in some areas the gas supplier will derate the gas," and Goodman tells installers to get the local heating value from the utility. That's why the right orifice depends on your actual gas, not just your elevation.
A careful installer confirms the result by clocking the gas meter: timing how long the furnace takes to burn one cubic foot and calculating actual input. Manuals warn not to derate by lowering manifold pressure below the nameplate setting, which can cause poor flame and condensation problems.
Pressure switches and high-altitude kits
Modern furnaces use an inducer fan and a pressure switch to prove the vent is drawing before the burners light. In thin air the inducer creates less pressure difference, so a sea-level switch may not close reliably. That causes nuisance lockouts on cold nights. High-altitude kits typically include a matched switch and orifices.
Colorado's NOx rules add another wrinkle. As covered in our Colorado furnace NOx rules guide, SWEEP noted that some ultra-low-NOx furnaces need a high-altitude conversion kit, estimated at $100–$200 in 2023.
Venting at altitude
Condensing furnaces (90%+ AFUE) vent through PVC pipe. Vent sizing tables in their manuals depend on pipe length, number of elbows and sometimes elevation. ACHR News reported one dealer's example in which a long vent run at altitude needed 3-inch PVC even though the furnace had a 2-inch outlet. Undersized vents can trip the pressure switch or, worse, spill exhaust. When a new condensing furnace replaces an old one that shared a chimney with the water heater, the water heater's venting may need to be resized too.
Air conditioners at altitude
An AC's outdoor coil rejects heat to outdoor air and its indoor coil absorbs heat from indoor air. Thinner air carries less heat on both sides. ACHR's example uses about 0.92 as the cooling adjustment at 5,000 feet, and says manufacturers should publish a derating factor for their equipment. ACHR's design example also illustrates the trade-off: more airflow helps capacity, but only if the ducts can move it at acceptable static pressure.
What this means for you:
- A "3-ton" AC delivers less than 3 tons at altitude unless the manufacturer's data says otherwise.
- Ducts sized by sea-level rules of thumb often can't move the extra cfm, so the AC loses capacity and the blower works harder.
- Upsizing by habit is not the answer either. An oversized system short-cycles. A load calculation with the altitude factor is.
If your AC struggles every summer, our AC not cooling guide walks through the checks. For a new system, see AC installation.
Heat pumps at altitude
Heat pumps face the same airflow penalty in both heating and cooling. The evidence:
- NREL lab tests in Golden (about 5,860 feet) measured about 5.5% less capacity for a ducted cold-climate heat pump and 7.4% less for a mini-split than at sea-level airflow, with COP down about 4.7% and 9%.
- ACCA Manual S guidance calls for about an 8–10% derate, a bit more than NREL measured.
- Fujitsu's bulletin for its Airstage heat pumps lists factors of 0.83 at 5,000 feet, 0.80 at 6,000, 0.77 at 7,000 and 0.74 at 8,000, for heating and cooling, and tells designers to size both indoor and outdoor units up accordingly.
The spread is wide, which is the point. Ask your contractor which manufacturer data they used. On top of altitude, heat pump output falls as outdoor temperature drops, so capacity at your county's design temperature (about 3–5°F for most of the metro, colder in Boulder County) matters most. Our heat pump sizing guide covers the Manual J and S steps, and Do heat pumps work in a Denver winter? covers cold-weather performance. For icing and defrost behavior, see Why is my heat pump covered in ice?
| Equipment | What altitude changes | What a proper install includes |
|---|---|---|
| Gas furnace | Less oxygen for combustion; inducer pressure lower; input must drop | Derate per manual, correct orifices or confirmed gas heat value, high-altitude pressure switch or kit, meter clocked, combustion analysis |
| Condensing furnace venting | Vent tables depend on length, elbows and sometimes elevation | Vent pipe sized from the manual for your run; water heater venting rechecked |
| Central AC | Less heat per cubic foot of air on both coils | Manufacturer altitude data, Manual J altitude factor, airflow verified against static pressure |
| Heat pump / mini-split | Capacity and efficiency drop in heating and cooling | Capacity at design temperature with altitude derate applied; balance point and backup sizing |
| Ductwork | More cfm needed for the same heat | Static pressure test; returns sized for the higher airflow |
Carbon monoxide: the safety side of altitude
An over-fired or poorly adjusted furnace at altitude is a recipe for incomplete combustion, and incomplete combustion makes carbon monoxide. Soot, a yellow or lazy flame, or frequent pressure switch lockouts are warning signs. The safeguards are simple:
- A combustion analysis at installation and during annual service, measuring CO and oxygen in the flue.
- Working CO alarms near every sleeping area, which Colorado law requires in many homes after a sale or permitted work.
- Prompt attention to venting changes, especially after a furnace or water heater replacement.
Our carbon monoxide and furnace safety guide covers the law, alarm placement and what to do if an alarm sounds. MrFixer also offers a carbon monoxide safety check.
- 1Confirm elevation and gas
Use the home's actual elevation and get the gas heating value from the utility.
- 2Apply the derate
Reduce input per the manual, commonly 4% per 1,000 ft of elevation above 2,000 ft.
- 3Install the kit
Fit high-altitude orifices and pressure switch where required. Never lower manifold pressure below nameplate.
- 4Size the vent
Use the manual's vent table for pipe length, elbows and elevation; recheck water heater venting.
- 5Clock the meter
Time the gas meter to confirm actual firing rate matches the derated input.
- 6Test combustion
Measure CO and oxygen in the flue and check temperature rise; record the readings.
Sizing: putting it together
Good sizing at altitude follows the same ACCA sequence as anywhere else, with altitude built in at each step:
- Manual J with your county's design temperatures and the altitude correction factor.
- Manual S using the manufacturer's expanded performance data with any altitude derate applied, and for furnaces the derated output, not the nameplate input.
- Manual D ducts sized for the higher airflow thin air requires.
- Commissioning: gas input clocked, combustion tested, refrigerant charge and airflow verified.
Two practical consequences. First, an 80,000 Btu/h furnace label overstates the heat it delivers here, so compare quotes on derated output. Second, because furnaces are typically oversized anyway, the derate rarely leaves a home short of heat, but it matters for tight new homes and for heat pumps sized close to the load.
Questions to ask your contractor
- What elevation did you use, and what altitude correction factor is in the load calculation?
- What is this furnace's derated input and output at my elevation?
- Does it need an orifice change or high-altitude pressure switch with our gas supply? Will you clock the meter?
- Will you do a combustion analysis at startup and leave me the readings?
- What capacity does this heat pump or AC deliver at my elevation and design temperature, according to the manufacturer?
- Will you measure static pressure and confirm the ducts can handle the airflow?
MrFixer Heating & Cooling is based in Castle Pines, at about 6,400 feet, and serves the Denver metro and foothills. We install and repair furnaces, heat pumps, mini-splits and dual-fuel systems, with free in-home estimates and financing available. If you have a quote and aren't sure altitude was handled, ask for a free second opinion, see our service areas, or call (720) 466-7983.
Frequently asked questions
- Do furnaces need to be adjusted for Denver's altitude? Yes. Furnace manuals require reducing gas input at altitude. Amana and Goodman call for 4% per 1,000 feet of elevation above 2,000 feet, about 21% at 5,280 feet, achieved with smaller orifices, a high-altitude pressure switch, or gas the utility delivers at lower heat content. The installer should confirm by clocking the meter and testing combustion.
- What is a high-altitude kit for a furnace? A manufacturer kit that adapts a furnace to thin air, typically smaller gas orifices and a pressure switch matched to the lower inducer pressure at altitude. Whether you need one depends on the model, your elevation and your gas supply.
- How much capacity does an AC or heat pump lose at 5,000 feet? It depends on the equipment. NREL measured 5.5–7.4% less heat pump capacity in Golden, ACCA guidance suggests 8–10%, and Fujitsu lists a 0.83 factor (17% less) at 5,000 feet for its Airstage heat pumps. Use the manufacturer's data for the model you're buying.
- Is Castle Rock or Evergreen different from Denver for HVAC? Yes. Castle Rock sits about 6,217 feet and Evergreen about 7,162 feet by USGS reference elevations, compared with 5,280 in Denver. Furnace derates and heat pump capacity corrections grow with elevation, and foothills homes often have colder design temperatures.
- Can altitude cause carbon monoxide problems? A furnace that isn't derated or adjusted for altitude can burn incompletely and produce more carbon monoxide. A combustion analysis at installation and annual service, plus working CO alarms, are the safeguards.
- Does altitude change what size furnace I need? It changes what a given furnace delivers. An 80,000 Btu/h-input furnace derated for altitude produces noticeably less heat than its label suggests, so compare quotes on derated output and base the size on a Manual J load calculation with Colorado design temperatures.
Sources (9)
- en.wikipedia.org en.wikipedia.org/wiki/List_of_Colorado_municipalities_by_elevation
- en.wikipedia.org en.wikipedia.org/wiki/Evergreen,_Colorado
- achrnews.com achrnews.com/articles/110408-selecting-heating-cooling-units-for-high-altitude-homes
- achrnews.com achrnews.com/articles/136057-furnaces-must-be-modified-for-high-altitude-applications
- manualslib.com manualslib.com/manual/796665/Amana-Gux-X.html?page=16
- manualslib.com manualslib.com/manual/738470/Goodman-Gms8.html?page=18
- images.greenbuildingadvisor.com images.greenbuildingadvisor.com/app/uploads/2016/09/25014433/001%20Altitude%20Capacity%20C
- nrel.gov nrel.gov/docs/fy24osti/89413.pdf
- energystar.gov energystar.gov/sites/default/files/asset/document/Design%20Temperature%20Limit%20Reference
We'll measure the house, run a load calculation and give you written prices for each option before any work starts.
Get a Free Estimate or call (720) 466-7983